Scottish Ecological Design Association The Scottish Executive
Scottish Ecological Design Association

Design and Detailing for Airtightness

home | introduction | context | designing | implementing | testing | details

3 Designing for Airtightness  


3.1 Performance Specification
3.2 Zones and Barriers
3.3 Design
3.4 Detailed Specification


pdf download options


Key Principles

1. A Performance Specification is a crucial document for establishing the appropriate targets for airtightness, along with the methodology for achieving it, and the roles and responsibilities of those involved.

2. Conceiving of a building in zones and air barriers will help all involved to visualise the task.

3. Air barriers must be impermeable, continuous, durable and accessible. They should be supported by positive mechanical seals where possible.

4. The simplest solutions will be the most buildable and durable.

5. A culture of airtight construction does not yet prevail and until it does, it may be necessary to follow up targets with specific details and specifications, along with guidance on the process of implementing the necessary level of co-ordination and attention to detail.

 


Unlike design for deconstruction (the subject of the first in this series of SEDA Guides) and the forthcoming guide on chemical-free design, the design of airtight buildings cannot be left to the specification and details, at least, not until the industry as a whole recognises the need and has sufficiently widespread experience. For the next few years, it will be necessary not only to provide careful details and performance specification, but also to develop thorough inspection and testing regimes, hence the need for Chapters 4 and 5 of this guide.

3.1 Performance Specification

The Performance specification may be the only document needed by the Architect / Designer / Client if the building is to be procured through Design and Build or similar route. However, it is more likely to be part of a suite of documents including detailed drawings.

The performance specification allows appropriate targets to be set for the project, along with a description of how the process is to be conducted, in terms of scheduling, audits and testing, and potentially remedial works. Given the increasing use of specialist subcontractors, particularly in larger projects, it is also critical that the performance specification sets out both the responsibility for, and constructive guidance regarding the co-ordination of trades with respect to the final air permeability of the completed envelope.

A sample specification clause is shown below, which could be adapted for specific use.

3.2 Zones and Barriers

Once appropriate targets have been set for the project, the next task is to identify zones which require greater or lesser airtightness levels. Ideally, these zones need to be identified on a drawing which also identifies the specific air barriers in red.

 


Sample Specification Clause

0 The contractor shall appoint specialist consultants who are members of the Air Tightness Testing and Measurement Association (ATTMA) to carry out the following works.
(delete as appropriate)

  • Design Review – to identify the air tight envelope and highlight any elements of work which may present a risk to the final air test failing.
  • Site Audits - A minimum of [ ___ ] site audits with the last site audit carried out 1 week (or more, as agreed) prior to the air tightness test
  • Air Leakage tests – A minimum of 2 tests; the first upon completion of a weathertight envelope, the last one week before practical completion
  • Suggested Specialists: [ ___ ]

1 Prior to the air tightness test, the Architect shall work out the envelope area as set out in BS EN 13829:2001(1)(7).

2 The air tightness test shall be carried out in line with BS EN 13829:2001(1).

3 The air tightness test result shall be expressed as an Air Permeability (units m3/h/m2 of total surface area @ 50 Pa)
and shall not exceed [ ___ ] m3/h/m2 @ 50 Pa.

4 The following conditions shall be met during the test;

  • External envelope shall be complete when the test is carried out. Raised floors and suspended ceilings shall have sufficient panels removed by the contractor to allow the free flow of air through them. Internal doors shall be wedged open.
  • All doors, windows and fixed vents shall be closed throughout the test.
  • Mechanical ventilation systems shall be temporarily sealed.
  • Smoke extracts and lift shaft vents shall not be sealed.
  • Drains and water traps shall be filled with water.
  • Any areas of temporary sealing or other deviations from the standard test procedure to be recorded in the test report.

5 If the building air leakage rate is > [ ___ ] m3/h/m2 @ 50 Pa,
[ the contractor shall arrange / the CA and Contractor shall agree ] (delete as appropriate) for appropriate remedial action to be taken which could include;
A site audit of the air tight envelope, while de-pressurised,
localised smoke leakage test, full scale smoke leakage test, thermographic survey, reductive sealing of components and building areas / elements to record their contribution.

6 Further tests shall be carried out until the air permeability is
< [ ___ ] m3/h/m2 @ 50 Pa.

7 The contractor shall arrange for a suitably competent specialist to carry out a thermographic survey to BS EN 13187:1999, to establish that insulation is continuous. (if appropriate for the construction type)

8 The contractor shall bear the cost of all air tightness works, tests and any remedial works.

9 The contractor shall operate a Quality Management System and be registered with a relevant body.

10 The contractor shall hold Professional Indemnity Insurance.

[Adapted from Information supplied by HRS Services, Sheffield]

 


For example, in the diagram below, an industrial unit with office space is divided into five separate zones, and air barriers are identified as required. Such a drawing, however diagrammatic initially, helps to conceive of the subsequent specification and detailing needs, giving an overview of the problem.

Showing conditioned (heated or cooled) areas as distinct from unconditioned

Showing conditioned (heated or cooled) areas as distinct from unconditioned, with overall airtight separation highlighted in red dashed lines. The example highlights the value of simplicity at an early stage; allowing unheated spaces to project into heated ones like this will complicate the process of constructing effective air barrier layers later.

Heated zones need to be kept separate from unheated zones such as roof voids, delivery bays etc. whilst service shafts may require particular attention. Boiler rooms with large flues and intake vents may need to be separated.

Entrances are often significant sources of draughts. Lobbies with doors set apart by around 4m, so that one door closes before the second is opened, can be effective, whereas in highly trafficked areas revolving doors are likely to be preferable. Tall buildings, with atria, stairways and service shafts all of which rise through the building can be prone to ‘stack effect’ air movement whereby warm air rises, dragging in cooler air from outside at the lower levels creating more acute air leakage problems. A number of tactics may be employed to reduce the effects, but in any event issues of airtightness are likely to be highlighted in these cases.



3.3 Design

With the zones and air barriers located, it is necessary to design the air barriers themselves.

To be effective, the air barrier must:

  • be made of suitably air impermeable materials;
  • be continuous around the envelope or zone
  • have sufficient strength to withstand any pressures created by wind, stack effect or air control systems
  • be easily installed
  • be durable
  • be accessible for maintenance / replacement if appropriate

The last of these is important since there is evidence that the airtightness of some constructions will tend to decrease over time, and in particular the first period after completion.

There are a number of strategic measures which can be employed to simplify the business of designing an airtight building. Since service penetrations in and out of a building provide a major source of air leaks, one strategy is to collect all such penetrations into one accessible area, see right.

In construction types such as steel and timber frame, it is usually wise to employ a specific membrane or layer as the air barrier, rather than rely on sealant between, for example, the sheathing boards. Such a membrane can usually double up as the vapour barrier if used internally and gives the Designer the opportunity to consider and address airtightness explicitly, rather than as a function of other elements. Bear in mind that most membranes are flimsy and will need support in all areas.

Another strategy is to employ service voids. Creating a service void internally allows for alteration and maintenance of services and finishes without recourse to penetrations through the air barrier. This allows for long term good performance in contrast to membranes which are liable to penetration at all service points, necessitating careful sealing of each and every penetration, not only initially, but over the years of alterations and maintenance to come.

Generally, it is better to conceive of the joints in airtight layers as ‘positively’ connected, anticipating differential movement and decay of adhesive or chemical bonds. For example, where different components of a curtain walling system are liable to differential movement, it is clear that a joint whereby the two components are held together with a positive mechanical connection across a compressed gasket is likely to remain airtight longer that a simple butt joint with a mastic sealant between.

Finally it is clear that complex solutions to airtightness are likely to be more prone to poor execution and potentially to greater vulnerability to differential movement, failure of sealants, dislocation of components and so on. It is important therefore to aim for the simplest solutions to providing an airtight layer, using the fewest separate materials, junctions and penetrations, and the easiest installation and maintenance.

It is worth making a point of considering each and every specified component with regard not only to its own intrinsic airtightness characteristics, but with regard to the connections between it and adjacent components. It is important to provide explicit details and guidance at specific, and particularly tricky detail areas. On design and build contracts it may be necessary to allow for some form of review of proposed solutions and procedures.

The following provide a few examples whereby airtightness can be simplified at the earliest design stages.

However good the workmanship, blockwork on its own can never be considered airtight. Once plastered, on the other hand, it may be considered extremely airtight, with concern only for those edges and corners where cracking or gaps can appear. This may be contrasted with the more common practice of drylining block walls with plasterboard on battens or dabs. In addition to the intrinsically non-airtight block wall behind, this form of construction typically gives rise to a wide range of air leakage paths behind the boards and into floor, partition wall and ceiling cavities. From the perspective of airtightness, drylining should be avoided unless great care is taken. See right.

Similarly, timber floors are difficult to seal well without a good deal of care. On the continent - and to an increasing extent in the UK at large - concrete floor systems are being used for both ground and first floors (often for other reasons such as acoustics, fire and the desire for underfloor heating) and these are easier to make adequately airtight. Hollow planks however can leak into cavities and require to be sealed at their ends.

One important and often quoted example is the timber first floor connection with a block wall inner leaf. Who is responsible for ensuring absolute airtightness when the timber joists rest on the wall and are infilled between with block and mortar? Presumably the bricklayer, but is it then his fault if the timber is installed at the wrong moisture level and subsequently twists and warps, leaving cracks around every joint? Is it really feasible to attempt to tape or mastic seal around them all, and what if the underside of the ceiling is to be exposed? (See right)

Far better perhaps, to do away with the joist-onto-wall detail altogether and replace with joist hangers(8). Increasingly, the designer should be seeking solutions which are intrinsically airtight because of the design, rather than continuing as before while accepting an increased use of duck tape and mastic on site! Whilst these may get you through the initial airtightness tests, they are are sort term solutions and not likely to lead to the anticipated energy savings for the Client in the long term.

A good review of the various materials and components which allow the Designer to create an air barrier may be found in the BRE Report BR448: Airtightness in Commercial and Public Buildings.

3.4 Detailed Specification

Beyond the performance specification illustrated earlier, it is important that the issue of airtightness becomes embedded within the standard specification vocabulary.

Where an equal or approved alternative may be allowed, it is critical that an airtightness performance specification is part and parcel of that equality of performance. For example, it may no longer remain satisfactory merely to specify a membrane, but in addition to specify the fairly precise nature of the sealing, overlapping and potentially the subsequent layers as well. Simply offering a performance specification and ensuring the responsibility resides with the Contractor is all very well, but it is important too to offer solutions that will enable a satisfactory outcome to be achieved.

Above the suspended ceiling, the plasterboard is not continuous nor sealed

Above the suspended ceiling, the plasterboard is not continuous nor sealed, and mineral wool has been used which is not in itself airtight. Source: A. Leaman & W. Bordass, www.usablebuildings.co.uk

Services Zones or Rooms enable a range of services to be collected together

Services Zones or Rooms enable a range of services to be collected together before exiting the building, allowing most of the penetrations in the external fabric to be grouped and sealed effectively. Source: C. Morgan

Service voids enable cables and pipework to be installed and altered without needing to penetrate the air barrier

Service voids enable cables and pipework to be installed and altered without needing to penetrate the air barrier. Note however that if they are not run in conduit, protection may be needed against subsequent fixings. Source: C. Morgan

Positive physical connections are to be preferred over any other joint such as one relying on adhesives

Positive physical connections are to be preferred over any other joint such as one relying on adhesives. In the timber frame example shown the air barrier membrane is shown lapped and sealed with mastic over a firm background (boards with stud behind) and with a positive mechanical fix - a batten - fixed over the top and through to the stud. Source: C. Morgan.

a problem of drylining is that it can create hidden pathways for air

In addition to the intrinsic lack of airtightness, a problem of drylining is that it can create hidden pathways for air, as above, into the void above suspended ceilings and elsewhere throughout the building. Source: P. Jennings.

Timber joists built into a block wall - a poor detail for airtightness

Timber joists built into a block wall - a poor detail for airtightness. Far better to use joist hangars and avoid the problem. Source: P. Warm.

here, hollow planks have been left ungrouted where they meet the external wall

Concrete planks are not free of problems either. here, hollow planks have been left ungrouted where they meet the external wall, which could lead to extensive air leakage internally. Source: P. Jennings.

ad hoc solutions on site are not likely to be durable - or elegant!

If not designed to be airtight in the first place, ad hoc solutions on site are not likely to be durable - or elegant! Source: C. Morgan


back to top | contents | next chapter

Footnotes:

7. It is likely that TM 23 is going to be revised and in the meantime UKAS approved testers (which must include ATTMA members) are testing instead to BS EN 13829:2001(1) Thermal Performance of Buildings: Determination of Air Permeability of Buildings - Fan Pressurisation Method.

8. Manthorpe Building products (01773 514 200) and www.manthorpe.co.uk produce a ‘joist seal’ or boot which allows joists to be built into block walls without the attendant disadvantages noted above.

back to top | contents | next chapter

   
Easyspace - your perfect partner for the web We would like to thank Easyspace for providing this web space free of charge. Easyspace give free web space to registered charities